HP33SM Subrack Modular UPS Series (40kVA-150kVA)
TECHNICAL SPECIFAICATION
|
MODULE MODEL
|
HP33SM-RM-40
|
HP33SM-RM-50
|
HP33SM-RM-60 |
CABINET MODEL
|
HP33SM-80 |
HP33SM-120 |
HP33SM-200 |
HP33SM-100 |
HP33SM-150 |
HP33SM-200 |
HP33SM-120 |
Cabinet capacity
|
40kVA~80kVA |
40kVA~120kVA |
40kVA~200kVA |
50kVA~100kVA |
50kVA~150kVA |
50kVA~200kVA |
60kVA~120kVA |
Module capacity
|
40kVA
|
50kVA |
60kVA |
Max. number
|
2+1 |
3 |
5 |
2+1 |
3 |
4 or 4+1 |
2+1 |
| INPUT |
| Voltage |
380/400/415Vac, (3Ph+N+PE) |
| Operating voltage range |
138~305Vac for 40% load; 305~485Vac for 100% load |
| Operating frequency range |
40Hz~70Hz |
| Power factor |
≥0.99 |
| Harmonic distortion (THDi) |
≤3% (100% Linear load) |
| Bypass voltage range |
Max. voltage: 220V: +25% (Optional +10%, +15%, +20%)
230V: +20% (Optional +10%, +15%)
240V: +15% (Optional +10%)
Min. voltage: -45% (Optional -10%, -15% -20%, -30%)
|
| Bypass frequency range |
Frequency protection range: ±10% |
| Power walk in |
Support |
| Generator input |
Support |
| OUTPUT |
| Rated voltage |
380/400/415Vac, (3Ph+N+PE) |
| Power factor |
1.0 |
| Voltage regulation |
±1% |
| Output frequency |
Line mode |
Synchronize with input, when the input frequency >±10%(±1%/±2%/±4%/±5% optional), output 50/60 (±0.1Hz) |
| Bat. mode |
(50/60±0.1%)Hz |
| Crest factor |
3:1 |
| Harmonic distortion (THDv) |
≤2% with linear load; ≤4% with nonlinear load |
| Efficiency |
96% |
BATTERY
|
| Battery voltage |
360Vdc~600Vdc |
| Battery type |
VRLA / Li |
| Power module charge current |
20A (Max.) |
SYSTEM FEATURES
|
| Transfer time |
Utility to Battery: 0ms; Utility to Bypass: 0ms |
| Overload |
Inverter mode |
≤110% 60min, ≤125% 10min, ≤150% 1min, >150% 1.2s shut down inverter |
| Bypass mode |
30℃: 135% for long term; 40℃: 125% for long term; >1000%, 100ms |
| Overheat |
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
| Low battery voltage |
Alarm and Switch off |
| Self-diagnostics |
Upon Power On and Software Control |
| Backfeed protection |
Support |
| Battery |
Advanced Battery Management |
| Noise suppression |
Complies with EN62040-3 |
| Audible & visual alarms |
Line Failure, Battery Low, Overload, System Fault |
| Status LED & LCD display |
Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault |
| Reading on the LCD display |
Input, Output, Battery, Command, Setting, Maintenance |
|
Communication interface (Optional)
|
RS232, RS485, Parallel, LBS, Dry contact port, Relay card, SNMP card , Battery temperature sensor
|
ENVIRONMENTAL
|
| Operating temperature |
0℃~40℃ |
| Storage temperature |
-25℃~55℃ |
| Humidity range |
0~95% (Non condensing) |
| Altitude |
<1000m, derating required when >1000m |
| Noise level |
<57dB |
<58dB |
<65dB |
<58dB |
<62dB |
<65dB |
<62dB |
PHYSICAL
|
| Dimension W×D×H |
UPS cabinet |
485×850×620mm |
485×965×887mm |
485×850×620mm |
485×965×887mm |
485×850×620mm |
| Power module |
440×620×130mm |
| Net weight |
UPS cabinet |
103kg |
204kg |
113kg |
210kg |
210kg |
98kg |
| Power module |
33kg |
34kg |
35kg |
STANDARDS
|
| Safety |
IEC/EN 62040-1, IEC/EN 62477-1 |
| EMC |
IEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11) |